Low voltage outdoor current transformers ELA N

Low voltage outdoor current transformers ELA N

ELA N current transformers are designed to supply circuits of power equipment measuring systems with maximal voltage of 0.72kV, for the cable, the bus-bar or bushing on the low voltage side of the transformer.

The current transformers can operate in the ambient temperature range from -35°C to + 40°C in indoor and outdoor conditions.

The secondary side terminals are led as a cable with specified cross section and length. The rated load is determined on the end of the cable.

The ELA N current transformers with 0,2; 0,5; 0,2S and 0,5S accuracy classes may be calibrated in the Central Office of Measures.

Ask for product

Technical data

Rated primary current Ipr = 75 ÷ 1500 A
Rated continous thermal current Icth = 120% * Ipn
Rated secondary current Isn = 5 A
Rated load S2n = 1 ÷ 2.5 VA
Accuracy class

0.2S; 0.5S; 0.2; 0.5
CT's ELA N may be calibrated in the Central Office of Measures

Rated short-time thermal current 1 sec. Ith = 60 * Ipr
Rated dynamic current Idyn = 2.5 * Ith
Rated frequency f = 50 ÷ 60 Hz
Maximal voltage Um = 0.72 kV
Rated test voltage Up = 3 kV
Factor security FS5
Degree of protection lP IP 44

Product specification

Type/Technical data Inside diameters Rated primary current Rated power Accuracy class Rated secondary current

ELA 1N

Download specification

Ø41 75 ÷ 1000 A 1 ÷ 2.5 VA 0.2S; 0.5S;
0.2; 0.5;
5 A

ELA 2N

Download specification

Ø60 200 ÷ 1500 A 1 ÷ 2.5 VA 0.2S; 0.5S;
0.2; 0.5;

ELA 3N

Download specification

Ø90 400 ÷ 1500 A 1 ÷ 2.5 VA 0.2S; 0.5S;
0.2; 0.5;