Low voltage, voltage transformers



The use of voltage transformer , enabling the indirect measurement of voltage , has on aim:

- assurance the staff operating measuring instruments and relays in the switching station safe conditions of the work
- enabling the standardization of measuring instruments and relays

Voltage transformers are designed for supplying measuring and protective circuits of electrical power devices.


a)Low voltage, voltage transformers US 1,2 type

 


Type I Type II
Rated voltage Accuracy
class
Rated
power
Rated voltage Accuracy
class
Rated
power
primary test secondary primary test secondary
V kV V - VA V kV V - VA
480 : √3 3 100 : √3 0.2 1 ÷ 5 1000 6 100 0.2 1 ÷ 2.5
690 : √3 6 100
220
230
380
400
500
600
3 100
 
110
 
220
 
230
0.5 5 ÷ 10
1200 : √3 6 1 ÷ 2.5
100 : √3
220 : √3
230 : √3
380 : √3
400 : √3
500 : √3
600 : √3
3 100 : √3
 
110 : √3
 
220 : √3
 
230 : √3
0.5 5 ÷ 10
1 5 ÷ 20 1 5 ÷ 20
660 : √3
690 : √3
750 : √3
1000 : √3
1140 : √3
1200 : √3
6 660
690
750
1000
1140
1200
6
3 5 ÷ 30 3 5 ÷ 30


Example of order :
I.  Voltage transformers  US 1,2 type; 400:√3/100:√3 V/V; rated power 10 VA; accuracy class 0.5; test voltage Up=3 kV
II.  Voltage transformers  US 1,2 type; 1000/100 V/V; rated power 15 VA; accuracy class 1; test voltage Up=6 kV

Attention!
Other parameters available on request.

 

b) Low voltage, voltage transformers US 1,2m type

 

Technical data:

Type I Type II
Rated voltage Accuracy
class
Rated
power
Rated voltage Accuracy
class
Rated
power
primary test secondary primary test secondary
V kV V - VA V kV V - VA
100 : √3
220 : √3
230 : √3
380 : √3
400 : √3
500 : √3
600 : √3
3 100 : √3
 
110 : √3
 
220 : √3
 
230 : √3
0.5 2.5 100
220
230
380
400
500
600
3 100
 
110
 
220
 
230
0.5 2.5
1 2.5 ÷ 3.75 1 2.5 ÷ 3.75
660 : √3
690 : √3
750 : √3
1000 : √3
6 660
690
750
1000
6
3 2.5 ÷ 7.5 3 2.5 ÷ 7.5
Example of order :
I. Voltage transformers US 1.2m type; 400:√3 / 100:√3 V/V; rated power 2.5 VA; accuracy class 0.5; test voltage Up=3 kV
II. Voltage transformers US 1,2m type; 1000 / 100 V/V; rated power 7.5 VA; accuracy class 1; test voltage Up=6 kV

Attention! Other parameters available on request.
Informations about other solutions and detailed technical informations are available in our Technical Department:
tel./fax: +48 22 815 67 17
e-mail: ,

Zakłady POLCONTACT WARSZAWA
ul. Goździków 26
04-231 Warszawa
Projekt & cms: www.zaler.pl