Low voltage protective current transformers

1. Transformers for cooperation with MiCOM P210 and P211 type relays from AREVA T&D:
  • IZK ... cable type
  • IZS ... bus-bar type
  • IZW ... with primary winding terminals

The parameters of the secondary winding were not passed for these transformers but only: transmissions, the type of the relay, and the section of the conductor and the maximum distances of the clamps of the relay from transformer.
 
Information for individual transformers was passed on sides 2; 3; 4 and 5 in technical data, guaranteeing protection class 5P and the Accuracy Limit Factor ALF=15. According to the PN-EN 60044-1 standards the admissible current error contains oneself in borders ± 1% with the rated burden and the rated current.
 
This assures the correct cooperation of the transformer with the relay in the protection system according to the diagram of No. 1 and No. 2


These arrangements are designed to the protection of motor before:

  • overload,
  • derating,
  • the asymmetry of phase currents,
  • the atrophy of phaze,
  • excessive growth of the temperature.

This variant has this advantage that the designer does not have to wonder over the proper selection transformer with the relay, because the correct working of this arrangement was confirmed in laboratory tests.
 
Complex transformer and relays it is possible to buy in factory prices both in our Company as and in AREVA T&D.

Technical data:

Type/Technical data Primary current
With primary winding
IZW 1; IZW 2 5 ÷ 300 A
cable type
IZK 1; IZK 2 50 ÷ 600 A
IZK 3 125 ÷ 1500 A
bus-bar type
IZS 1; IZS 2; IZS 3 150 ÷ 2000 A



The example of application for direct starting with utilization of the protections of the motors of the type MiCOM P210 (the version: 4-19,75 A , 230 V AC) or P211 (the version: 4-6 A , 230 V AC or 24-230 V AC/DC) cooperating with the transformers of the type IZK or IZS:
Diagram no. 1 
 
The example of application for starting with "delta-WYE" with utilization of the protections of the motors of the type MiCOM P210 (the version: 4-19,75 A , 230 V AC) or P211 (the version: 4-6 A , 230 V AC or 24-230 V AC/DC) cooperating with the transformers of the type IZK or IZS:
Diagram no. 2
 
2. Transformers to the power supply the every kind of protection relays:

  • IZK ...U  cable type
  • IZS ...U  bus-bar type 
  • IZW ..U  with primary winding terminals

The transformers are made in definite powers, in the protection classes 5P and 10P with the Accuracy Limit Factor ALF=5; 10; 15.

Technical data:



Type/Technical data Primary current Rated power Accuracy class
with primary winding
IZW 1U 5 ÷ 300 A 1 ÷ 5 VA 5P 15 ÷ 10P 15
IZW 2U 5 ÷ 300 A 3,5 ÷ 10 VA 5P 10 ÷ 10P 15
cable type
IZK 1U 75 ÷ 400 A 1 ÷ 15 VA 5P 5 ÷ 10P 15
IZK 2U 50 ÷ 600 A 1 ÷ 15 VA
IZK 3U 50 ÷ 1000 A 1 ÷ 15 VA
bus-bar type
IZS 1U 150 ÷ 250 A 1 ÷ 5 VA 5P 5 ÷ 10P 15
IZS 2U 100 ÷ 500 A 1 ÷ 7,5 VA
IZS 3U 400 ÷ 2000 A 1,25 ÷ 15 VA
IZS 30U 100 ÷ 1500 A 1 ÷ 20 VA
IZS 31U 100 ÷ 1500 A 1 ÷ 25 VA
IZS 4U 200 ÷ 1500 A 1 ÷ 20 VA


 

Informations about other solutions and detailed technical informations are available in our Technical Department: