Current-voltage converters AC/DC 



Current-voltage converters AC/DC transform primary alternating current Ipn to rated secondary direct voltage Usn. They are designed for supplying measuring and protective circuits of electrical power devices.

Current converters transform alternating primary current up to 120% value with accuracy ± 3% in range from 20% to 120%.
 

Advantage of our current transformers is rated short-time thermal current (1 second): Ith = 60 * Ipn.
The secondary circuit of current-voltage converter should be loaded according to technical data or should be opened.

Informations about other solutions and detailed technical informations are available in our Technical Department:
tel./fax: +48 22 815 67 17
e-mail: ,

Technical data:

Rated secondary direct voltage         Usn= 1 V; 2 V; 5 V; 10 V; 15 V
Rated primary alternating current Ipn= 1 ÷ 3000 A
Permanent overload Ipn= ext. 120%
Rated burden S2n = 5 ÷ 75 kW
Accuracy

±3%

Rated short-time thermal current 1 sec. r.m.s. Ith = 60 * Ipn
Rated dynamic current 
(for converters with primary winding and cable type)l
Idyn = 2.5 * Ith
Rated dynamic current 
(for bus bar type converters)
depends on circuit (practically unlimited) 
Rated frequency f = 50 ÷ 60 Hz
Max. voltage Um = 0.72 lub 1.2 kV
Test voltage Up = 3 lub 6 kV


Type/Technical data Primary current Rated secondary 
direct voltage
Accuracy
with primary winding
EULA 0d 1 ÷ 20 A 1 V; 2 V; 5 V; 10 V; 15 V ±3%
EULA 1d W20 5 ÷ 300 A
cable type
EULA 0d 50 ÷ 150 A 1 V; 2 V; 5 V; 10 V; 15 V ±3%
EULA 1d 50 ÷ 600 A
bus-bar type
IUSN 1d 50 ÷ 800 A 1 V; 2 V; 5 V; 10 V; 15 V ±3%
IUSN 2d 100 ÷ 1250 A
IUSN 3d 400 ÷ 2000 A
IUSN 30d 300 ÷ 2000 A
IUSN 31d; IUSN 32d 500 ÷ 3000 A
IUSN 4d 500 ÷ 3000 A

 

Zakłady POLCONTACT WARSZAWA
ul. Goździków 26
04-231 Warszawa
Projekt & cms: www.zaler.pl